Loading...
9 Tabular overview of the program procedures Charge
© Nortec Electronics 2018 65
9.3 Charge
With program „Charge“ the batteries are charged according to manufacturers instructions.
Examples:
Lead battery
NiCd-battery
================================
COPYRIGHT
NORTEC
2014-15 UL60 V 1.0 16.06.15
SN: 160001
--------------------------------
DATE: 28.06.15
BATTERY NO:
OPERATOR NO:
NOM. VOLTAGE: 12.00 V
RATED CAP: 100.0 Ah
PROGRAM: 210
Pb battery sealed MIL
Charge
--------------------------------
PROGRAM START 10:00:02
VOLTAGE = 12.21 V
--------------------------------
P210:S1: 10:03:53
TOPPING CHARGE
VOLTAGE = 14.40 V
CURRENT = 40.01 A
CAPACITY = 002.0 Ah
= 002 %
TIME = 003 MIN
--------------------------------
P210:S2: 12:03:53
I-CHARGE
VOLTAGE = 14.40 V
CURRENT = 40.01 A
CAPACITY = 82.07 Ah
= 082 %
TIME = 120 MIN
--------------------------------
P210:S3: 13:07:53
U-CHARGE
VOLTAGE = 14.40 V
CURRENT = 02.01 A
CAPACITY = 100.7 Ah
= 100 %
TIME = 184 MIN
--------------------------------
P210:S4: 15:08:25
TOPPING CHARGE
VOLTAGE = 14.40 V
CURRENT = 1.21 A
CAPACITY = 103.0 Ah
= 103 %
TIME = 120 MIN
--------------------------------
PROGRAM AUTOMATICALLY FINISHED
================================
Only for deep discharged batteries
================================
COPYRIGHT
NORTEC
2014-15 UL60 V 1.0 16.06.15
SN: 160001
--------------------------------
DATE: 28.06.15
BATTERY NO:
OPERATOR NO:
NOM. VOLTAGE: 24.00 V
RATED CAP: 040.0 Ah
PROGRAM: 222
NiCd battery SAFT
Charge
--------------------------------
PROGRAM START 08:13:02
VOLTAGE = 25.09 V
--------------------------------
P222:S1: 09:17:36
I-CHARGE
VOLTAGE = 31.39 V
CURRENT = 40.01 A
CAPACITY = 042.7 Ah
= 106 %
TIME = 064 MIN
--------------------------------
P222:S2: 13:02:43
TOPPING CHARGE
VOLTAGE = 33.00 V
CURRENT = 04.01 A
CAPACITY = 057.7 Ah
= 144 %
TIME = 225 MIN
--------------------------------
CELL 01: 1.612 V
CELL 02: 1.610 V
CELL 20: 1.600 V
--------------------------------
P222:S2: 13:17:36
TOPPING CHARGE
VOLTAGE = 32.99 V
CURRENT = 04.01 A
CAPACITY = 058.7 Ah
= 146 %
TIME = 240 MIN
--------------------------------
PROGRAM AUTOMATICALLY FINISHED
================================

Table of Contents