8-93
8 Pulse Outputs
CJ2M CPU Unit Pulse I/O Module User’s Manual
8-11 Pulse Output Patterns
8
8-11-2 Positioning Control (Independent Mode)
Stopping a Pulse Output
Operation
Example
application
Frequency changes Function
Procedure
Instructions Settings
Stop pulse
output
(Number of
pulses set-
ting is not
preserved.)
Immediate
stop
Stops the pulse output immedi-
ately. Clears the current num-
ber of output pulses.
PULS
↓
ACC (Inde-
pendent) or
SPED (Inde-
pendent)
↓
INI
Stopping
pulse output
PLS2
↓
INI
Stop pulse
output
(Number of
pulses set-
ting is not
preserved.)
Immediate
stop
Stops the pulse output immedi-
ately. Clears the current num-
ber of output pulses.
PULS
↓
SPED (Inde-
pendent)
↓
SPED (Inde-
pendent)
•Port
• Indepen-
dent
• Target fre-
quency = 0
Stop sloped
pulse out-
put
smoothly.
(Number of
pulses set-
ting is not
preserved.)
Decelerate
to a stop
Decelerates the pulse output
to a stop.
If ACC(888) started the opera-
tion, the original accelera-
tion/deceleration rate will
remain in effect.
If SPED(885) started the oper-
ation, the acceleration/deceler-
ation rate will be invalid and
the pulse output will stop
immediately.
PULS
↓
ACC or SPED
(Independent)
↓
ACC (Inde-
pendent)
•Port
• Indepen-
dent
• Target fre-
quency = 0
PLS2
↓
ACC (Inde-
pendent)
Pulse frequency
Present
frequency
SPED
instruction
executed
INI
instruction
executed
Time
Pulse frequency
Present
frequency
SPED
instruction
executed
SPED
instruction
executed
Time
Pulse frequency
Present
frequency
Target
frequency=0
Original acceleration/
deceleration rate
ACC instruction executed.
Time