6 Interrupts
CJ2M CPU Unit Pulse I/O Module User’s Manual
6-2 Interrupt Inputs
6
6-2-2 Application Procedure
6-2-2 Application Procedure
1
Select Quick-response Input in the Quick-response
Input Detailed Settings Dialog Box that is accessed from
the I/O Module Tab Page of the PLC Setup using the
CX-Programmer.
This will allocate inputs IN00 to IN03 or IN10 to IN13 for
interrupt inputs.
Specify when changing from PROGRAM mode to RUN
mode whether to detect ON or OFF transitions in inputs.
Specify whether to latch the PV of a pulse output/high-
speed counter when an interrupt task is started.
2
When using Counter Mode, set the counter set values
for interrupt input counters 0 to 7 in Auxiliary Area words
A532 to A535 and A544 to A547.
3
Write the program in the interrupt task. Interrupt tasks
140 to 147 correspond to IN00 to IN03 and IN10 to
IN13. The following are specified using two MSKS(690)
instructions.
Specify whether to detect OFF or ON transitions to use
a different setting from the one in the PLC Setup.
Specify N to 110 to 117 in the MSKS(690) instruction.
Select the type of interrupt input (Direct Mode or
Counter Mode). If Counter Mode is selected, select
Increment or Decrement Counter Mode and enable
interrupts. Set N to 100 to 107 in the MSKS(690)
instruction.
6-2-3 Specifications
Item Direct Mode Counter Mode
Number of interrupt inputs 8 inputs
Allocated bit CIO 2960 and CIO 2962, bits 00 to 03
Interrupt detection method ON-to-OFF or OFF-to-ON transitions
Interrupt task numbers 140 to 147 (fixed)
Counting method --- Incrementing or decrementing
(Set with the MSKS(690) instruction.)
Counting range --- 0001 to FFFF hex (16 bits)
(Set in A532 to A535 and A544 to A547.)
Response frequency --- Single-phase: 3 kHz x 8 inputs
Storage locations for PVs for
interrupt inputs in Counter Mode
--- A536 to A539 and A548 to A551
PLC Setup
Set parameters in the Auxiliary
Area (for Counter Mode only).
Create interrupt
tasks.
Execute MSKS in
a cyclic task.
Create
ladder
program.

Table of Contents

Other manuals for Omron CJ2H-CPU6*-EIP Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CJ2H-CPU6*-EIP Series and is the answer not in the manual?

Omron CJ2H-CPU6*-EIP Series Specifications

General IconGeneral
BrandOmron
ModelCJ2H-CPU6*-EIP Series
CategoryController
LanguageEnglish

Related product manuals