6-3
6 Interrupts
CJ2M CPU Unit Pulse I/O Module User’s Manual
6-2 Interrupt Inputs
6
6-2-1 Overview
6-2 Interrupt Inputs
Interrupt inputs can be used in either Direct Mode or Counter Mode.
Interrupt Input in Direct Mode:
A corresponding interrupt task can be executed when an Pulse I/O Module input turns ON or turns OFF.
The PLC Setup or MSKS(690) instruction determines whether the interrupt is triggered when the input
turns ON or when it turns OFF.
Interrupt Input in Counter Mode:
A corresponding interrupt task can be executed when the number of times the Pulse I/O Module input
turns ON or turns OFF reaches the set value (A532 to A535 and A544 to A547) in Increment Mode, or
when it reaches zero in Decrement Mode.
The number of the interrupt tasks started by interrupt inputs must be between 140 and 147.
6-2-1 Overview
END
END
Interrupt input
Or when the ON or OFF count is
counted out (for Increment or
Decrement Mode)
CJ2M CPU Unit
Pulse I/O Module
Connecting
Cable
Connector-Terminal Block
Conversion Unit
Interrupt input turns ON or OFF (Direct Mode)
Cycle
Cyclic task
(ladder program)
I/O refresh
Interrupt occurs.
Interrupt task
Ladder program

Table of Contents

Other manuals for Omron CJ2H-CPU6*-EIP Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CJ2H-CPU6*-EIP Series and is the answer not in the manual?

Omron CJ2H-CPU6*-EIP Series Specifications

General IconGeneral
BrandOmron
ModelCJ2H-CPU6*-EIP Series
CategoryController
LanguageEnglish

Related product manuals