PLC Setup Appendix G
Origin Return Settings
Built-in AD/DA: Built-in Analog I/O Settings
Base Settings
AD 0CH/AD 1CH/AD 2CH/AD 3CH: Analog Input Settings
Name Default Settings When setting is read
by CPU Unit
Internal
address
Bits Settings
1 Speed 0 pps
(disabled)
1 pps At start of operation 413 and
412
00 to 15 0000 0001
hex
: :
100,000 pps (maxi-
mum for X/XA CPU
Unit)1,000,00 0 pps
(maximum for Y
CPU Unit)
0000 7530
hex
2 Acceleration Ratio 0 (disabled) 1 (pulses/4 ms) At start of operation 414 00 to 15 0001Hex
: :
65535
(pulses/4 ms)
FFFF hex
3 Deceleration Ratio 0 (disabled) 1 (pulses/4 ms) At start of operation 415 00 to 15 0001 hex
: :
65535
(pulses/4 ms)
FFFF hex
Name Default Settings When setting is read
by CPU Unit
Internal
address
Bits Settings
1 Built-in analog resolution
(for all analog I/O)
6,000
(Resolution)
6,000 (Resolution) When power is turned
ON
75 15 0
12,000 (Resolution) 1
Name Default Settings When setting is read
by CPU Unit
Internal
address
Bits Settings
1 Analog Input 0: Use Do not use. Do not use. When power is turned
ON
76 7 0
Use. 1
1-1 Range −10 to 10 V −10 to 10 V When power is turned
ON
76 00 to
02
0 hex
0 to 10 V 1 hex
1 to 5 V 2 hex
0 to 5 V 3 hex
0 to 20 mA 4 hex
4 to 20 mA 5 hex
1-2 Use averaging Do not use. Do not use. When power is turned
ON
76 6 0
Use. 1
2 Analog input 1: Use Do not use. Do not use. When power is turned
ON
76 15 0
Use. 1
2-1 Range −10 to 10 V −10 to 10 V When power is turned
ON
76 08 to
10
0 hex
0 to 10 V 1 hex
1 to 5 V 2 hex
0 to 5 V 3 hex
0 to 20 mA 4 hex
4 to 20 mA 5 hex
2-2 Use averaging Do not use. Do not use. When power is turned
ON
76 14 0
Use. 1