EasyManua.ls Logo

Omron NJ501-1500

Omron NJ501-1500
990 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A-19
Appendices
NJ-series Instructions Reference Manual (W502)
A-2 Error Code Descriptions
App
16#040D Illegal Unit Speci-
fied
The Unit specified for an
instruction does not exist.
A Unit that does not exist in the Unit configu-
ration information was specified.
A Unit that is in the Unit configuration infor-
mation was specified, but the Units does not
actually exist in the Controller.
page A-28
16#040F Unit Restart Failed Restarting a Special I/O
Unit or CPU Bus Unit failed.
The Special I/O Unit or CPU Bus Unit is pro-
cessing data.
page A-29
16#0410 Text String Format
Error
The text string input to an
instruction is not correct.
The text string that is input to the instruction
for conversion to a number does not repre-
sent a number or it does not represent a
positive number.
The input text string does not end in NULL.
page A-29
16#0411 Illegal Program
Specified
The program specified for
an instruction does not
exist.
The program specified by the function does
not exist (e.g., it was deleted).
page A-29
16#0413 Undefined CJ-
series Memory
Address
The required specification
is missing for a variable for
which CJ-series Unit mem-
ory must be specified.
The required AT specification is missing for
a variable for which CJ-series Unit memory
must be specified.
page A-30
16#0414 Stack Underflow There is no data in a stack. An attempt was made to read data from a
stack that contains no data.
page A-30
16#0416 Illegal Number of
Array Elements or
Dimensions
The valid range was
exceeded for the number of
array elements or dimen-
sions in an array I/O param-
eter for an instruction.
The valid range was exceeded for the num-
ber of array elements or dimensions in an
array I/O parameter for an instruction.
page A-30
16#0417 Specified Task
Does Not Exist
The task specified for the
instruction does not exist.
The specified task does not exist. page A-30
16#0418 Unallowed Task
Specification
An unallowed task was
specified for an instruction.
The local task, the primary periodic task, or
a periodic task was specified.
page A-31
16#0419 Incorrect Data
Type
A data type that cannot be
used for an instruction is
specified for an input or in-
out variable.
A data type that cannot be used for an
instruction is specified for an input or in-out
variable.
page A-31
16#041A Multi-execution of
Instructions
Multi-execution was speci-
fied for an instruction that
does not support it.
Execution of an instruction that does not
support multi-execution of instructions was
specified more than once.
page A-31
16#0800 FINS Error An error occurred when a
FINS command was sent
or received.
An error occurred when a FINS command
was sent or received.
page A-32
16#0801 FINS Port Already
in Use
The FINS port is being
used.
The FINS port is being used. page A-32
16#0C00 Illegal Serial Com-
munications Mode
The Serial Communica-
tions Unit is not in the serial
communications mode
required to execute an
instruction.
The serial communications port for the
Serial Communications Unit is not set to the
mode expected by the instruction.
page A-32
16#0C02 Port Setup Already
Busy
A Change Port Setup
instruction was executed
during execution of another
Change Port Setup instruc-
tion.
A Change Port Setup instruction was exe-
cuted during execution of another Change
Port Setup instruction.
page A-33
16#1400 SD Memory Card
Access Failure
SD Memory Card access
failed when an instruction
was executed.
An SD Memory Card is either not inserted
or is not inserted properly.
The SD Memory Card is broken.
The SD Memory Card slot is broken.
page A-33
16#1401 SD Memory Card
Write-protected
An attempt was made to
write to a write-protected
SD Memory Card when an
instruction was executed.
An attempt was made to write to a write-pro-
tected SD Memory Card.
page A-33
Error code Name Meaning Assumed cause Reference

Table of Contents