5 I/O Memory
5-22
CP2E CPU Unit Software User’s Manual(W614)
z Range of Values
The contents of Data Registers are treated as signed binary data and thus have a range of –32,768
to 32,767.
The content of Data Registers cannot be accessed (read or written) from the CX-Programmer.
z Data Register Initialization
The Data Registers will be cleared in the following cases:
• The operating mode is changed from PROGRAM mode to RUN/MONITOR mode or vice-versa
and the IOM Hold Bit is OFF.
• The PLC’s power supply is cycled and the IOM Hold Bit is OFF or not set to be held in the PLC
Setup.
• A fatal error occurs (except for one created with FALS).
Note If the IOM Hold Bit (A500.12) is ON, the Data Registers will not be cleared when a FALS error
occurs or the operating mode is changed from PROGRAM mode to RUN/MONITOR mode or
vice-versa.
Precautions for Correct UsePrecautions for Correct Use
• Do not use Data Registers until a value has been set in the register. The register's operation
will be unreliable if they are used without setting their values.
• The values in Data Registers are unpredictable at the start of an interrupt task. When a Data
Register will be used in an interrupt task, always set a value in the Data Register before using
the register in that task.
Hexadecimal content Decimal equivalent
8000 to FFFF –32,768 to –1
0000 to 7FFF 0 to 32,767

Table of Contents

Other manuals for Omron SYSMAC CP Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CP Series and is the answer not in the manual?

Omron SYSMAC CP Series Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CP Series
CategoryComputer Hardware
LanguageEnglish

Related product manuals