14 Serial Communications
14-10
CP2E CPU Unit Software User’s Manual(W614)
14-3 No-protocol Communications with
General Components
CP2E CPU Units and general devices with serial communications ports can be used for no-protocol
communications.
No-protocol communications enable sending and receiving data using the TRANSMIT (TXD) and
RECEIVE (RXD) instructions without using a protocol and without data conversion (e.g., no retry pro-
cessing, data type conversion, or process branching based on received data).
The serial communications mode is set to RS-232C.
No-protocol communications are used to send data in one direction to or from general external devices
that have an RS-232C or RS-422A/485 port using TXD or RXD.
For example, simple (no-protocol) communications can be used to input data from a barcode reader or
output data to a printer.
The following table lists the no-protocol communication functions supported by CP2E PLCs.
Note 1 Because the built-in RS-485 port of the Sîš…îš…-type CPU Unit and the RS-485 port of CP2W-CIFD2/CIFD3
use 2-wire connections, so they can only communicate in half duplex. Communications are not possible in
full duplex.
14-3-1 Overview
Communica-
tions
Transfer
direction
Method
Max.
amount of
data
Frame format
Other functions
Start code End code
Data
transmission
PLC →
External
device
Execution
of TXD in
the ladder
program
256 bytes Yes: 00 to FF
hex
No: None
Yes: 00 to FF
hex or CR+LF
No: None (The
amount of data
to receive is
specified
between 1 and
256 bytes when
no end code is
specified.)
• Send delay time (delay
between TXD execution and
sending data from specified
port): 0 to 99,990 ms at the
minimum(unit: 10 ms)
• Controlling RS and ER signals
Data
reception
External
device →
PLC
Execution
of RXD in
the ladder
program
256 bytes Monitoring CS and DR signals
CP2E CPU Unit
Sending/
receiving data
TXD or RXD
RS-232C or RS422A/485
General component
(e.g., barcode reader)

Table of Contents

Other manuals for Omron SYSMAC CP Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CP Series and is the answer not in the manual?

Omron SYSMAC CP Series Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CP Series
CategoryComputer Hardware
LanguageEnglish

Related product manuals