12 Pulse Outputs
12-44
CP2E CPU Unit Software User’s Manual(W614)
12-7 Reading the Pulse Output Present
Value
The present value of a pulse output can be read in the following two ways.
The PV that is stored in the following words can be read using the MOVL instruction or other instruc-
tions.
z Reading the Pulse Output PV with a PRV Instruction
• Value refreshed at the I/O refresh timing Æ Read PV from Auxiliary Area.
• Value updated when a program is executed Æ Read PV by executing a PRV instruction.
Reading the PV Refreshed at the I/O Refresh Timing
Read PV Auxiliary Area words
Pulse output 0 A277 (upper digits) and A276 (lower digits)
Pulse output 1 A279 (upper digits) and A278 (lower digits)
Pulse output 2 A53 (upper digits) and A52 (lower digits)
Pulse output 3 A55 (upper digits) and A54 (lower digits)
Reading the Value When a Program is Executed
#0000
#0000
D100
D100
D101
@PRV
15
0
Pulse output PV that was read
C1: Port specifier (example for pulse output 0)
C2: Control data (example for reading PV)
D: First destination word
Present value data lower bytes
Present value data upper bytes
Execution condition

Table of Contents

Other manuals for Omron SYSMAC CP Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CP Series and is the answer not in the manual?

Omron SYSMAC CP Series Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CP Series
CategoryComputer Hardware
LanguageEnglish

Related product manuals