14-17
14 Serial Communications
CP2E CPU Unit Software User’s Manual(W614)
14-4 Modbus-RTU Easy Master Function
14
14-4-3 Setting and Word Allocation
When the Modbus-RTU communication abnormality occurs, the following bits are turned ON.
A638 02 Serial Port 1 (EX) of CP2E
Nîš…îš…-type CPU Unit
Modbus-RTU Master Execution Error Flag
ON: Execution error.
OFF: Execution normal or still in progress.
01 Modbus-RTU Master Execution Normal Flag
ON: Execution normal.
OFF: Execution error or still in progress.
00 Modbus-RTU Master Execution Bit
Turned ON: Execution started
ON: Execution in progress.
OFF: Not executed or execution completed.
Address Name Contents
A392.04 Serial Port 1/Built-in RS-232C Port
Communication Error Flag
Turns ON when a timeout error, an overrun error, a
framing error or a parity error occurs on Modbus-RTU
Easy Master with serial port 1 or built-in RS-232C port.
A392.12 Serial Port 2/Built-in RS-485 Port Com-
munication Error Flag
Turns ON when a timeout error, an overrun error, a
framing error or a parity error occurs on Modbus-RTU
Easy Master with serial port 2 or built-in RS-485 port.
A50.04 Serial Port 1(EX) Communication Error
Flag
Turns ON when a timeout error, an overrun error, a
framing error or a parity error occurs on Modbus-RTU
Easy Master on serial port 1(EX).
Word Bit Port Contents

Table of Contents

Other manuals for Omron SYSMAC CP Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CP Series and is the answer not in the manual?

Omron SYSMAC CP Series Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CP Series
CategoryComputer Hardware
LanguageEnglish

Related product manuals