EasyManuals Logo

Omron SYSMAC CP Series User Manual

Omron SYSMAC CP Series
578 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #485 background image
A-25
Appendices
CP2E CPU Unit Software User’s Manual(W614)
A-1 Instruction Functions
App
A-1-10 Conversion Instructions
DATA
DECODER
MLPX @ Reads the numerical value in the specified digit (or byte) in the
source word, turns ON the corresponding bit in the result word (or
16-word range), and turns OFF all other bits in the result word (or
16-word range).
C: Control Word
4-to-16 bit decoder
8-to-256 bit conversion
Instruction Mnemonic Variations Symbol/Operand Function
MLPX(076)
S
C
R
S: Source word
C: Control word
R: 1st result word
R+1
R+14
R+15
R+16
R+17
R+30
R+31
R
R+1
C
C
Two 16-word ranges
are used when
l
specifies 2 bytes.
8-to-256 bit decoding
(Bit m of R to R+15 is turned ON.)
n=1 (Start with first byte.)
8-to-256 bit conversion
l
=1 (Convert 2 bytes.)
n=2 (Start with second digit.)
4-to-16 bit decoding
(Bit m of R is turned ON.)
l
=1 (Convert 2 digits.)
4-to-16 bit conversion
C0
8111215
ln
03
47
Conversion process
0: 4-to-16 bits (digit to word)
Always 0.
Number of digits/bytes to be converted
0 to 3 (1 to 4 digits)
Specifies the first digit/byte
to be converted
0 to 3 (digit 0 to 3)
C1
8111215
ln
03
47
Conversion process
1: 8-to-256 bits (byte to 16-word range)
Always 0.
Number of digits/bytes to be converted
0 or 1 (1 or 2 bytes)
Specifies the first digit/byte
to be converted
0 or 1 (byte 0 or 1)

Table of Contents

Other manuals for Omron SYSMAC CP Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CP Series and is the answer not in the manual?

Omron SYSMAC CP Series Specifications

General IconGeneral
ManufacturerOmron
MountingDIN Rail
CategoryProgrammable Logic Controller (PLC)
Programming LanguagesFunction Block Diagram, Structured Text, Sequential Function Chart, Instruction List
Communication ProtocolsEtherNet/IP, DeviceNet, CompoNet, RS-232C, RS-485
I/O Points10 to 160
Power Supply100-240 VAC or 24 VDC
Operating Temperature0°C to 55°C
Humidity10% to 90% (non-condensing)
Vibration Resistance10 to 57 Hz, 0.075 mm amplitude
Shock Resistance147 m/s², 3 times in each direction (X, Y, Z)

Related product manuals