Settings for energy saving
Energy saving
6
Set other indoor units.
z Repeat steps 3 to 5.
7
Touch [Reg.].
z To cancel the settings, touch [Cancel].
7
Item Explanation
Return temperature
Return time
Set the return temperatures for “Heat”,
“Cool”, and “Auto” and the return time.
Use
to set the temperature
or time.
The setting ranges are as follows.
y Return temperature for heating:
16 to 30 °C*
1
(1 °C intervals)
*1 The upper limit temperature for
some models is 26 °C.
y Return temperature for cooling (dry):
18 to 30 °C (1 °C intervals)
y Return temperature for auto:
17 to 27 °C (1 °C intervals)
y Return time (shared):
0 to 240 minutes (5 minute intervals)
Auto return The auto return function is enabled for
the selected indoor unit if you put a check
mark here.
The following items are settings common to all indoor units.
y Eco dirc. only
y Always return
Select the conditions for return.
When you select “Eco dirc. only”, the
return to the set temperature only occurs
automatically if it saves energy.
y Allow auto C/H
y Fan switching
When you select “Allow auto C/H”,
temperature auto return control also
occurs in the automatic mode.
When you select “Fan switching”, when
the running mode of the indoor units is
switched to “Auto Cool/Heat” the mode
switches from automatic mode to fan
mode, irrespective of the return time.
5
Touch [Register].
z The “Setting” dialogue closes.
z To cancel the settings, touch [Cancel].
5
Automatically return to set temperatures [Set temp. auto return]