Real-time clock
Real-time clock accuracy 1.73 s/day = 20 ppm at 25°C
Power reserve 240 h
Error messages to the higher-level controller or computer system
None
Programming
Programming tool PLCnext Engineer (2020.0)
Eclipse
MATLAB
®
Simulink
®
Supported programming languages Programming in accordance with IEC 61131-3
C++
C#
Java
Manufacturer-specific
IEC 61131 runtime system
Module classification PLCnext Control for direct control of Axioline F I/Os
Type of application Distributed control technology
Application interface OPC UA
Number of data blocks Depends on mass storage
Number of control tasks
AXC F 1152 8
AXC F 2152 32 (16 per processor core)
Cycle time
AXC F 1152 5 ms (for cyclic task)
AXC F 2152 1 ms (for cyclic task)
Program memory 8 MBytes
Retentive mass storage 48 kB (NVRAM)
Mass storage 16 MBytes
Parameterization memory Min. 4 MB (depending on storage medium)
Conformance with EMC directive 2014/30/EU
Immunity test in accordance with EN 61000-6-2
Electrostatic discharge (ESD)
EN 61000-4-2/IEC 61000-4-2
Criterion B, 6 kV contact discharge, 8 kV air discharge
Electromagnetic fields EN 61000-4-3 / IEC 61000-4-3 Criterion A, field strength: 10 V/m
Fast transients (burst) EN 61000-4-4/
IEC 61000-4-4
Criterion B, 2 kV
Transient overvoltage (surge)
EN 61000-4-5/IEC 61000-4-5
Criterion B; DC supply lines: ±0.5 kV/±0.5 kV (symmetri-
cal/asymmetrical), fieldbus cable shielding: ±1 kV
Conducted disturbance variables EN 61000-4-6/
IEC 61000-4-6
Criterion A, test voltage 10 V
Noise emission test in accordance with EN 61000-6-3 Class B

Table of Contents

Other manuals for Phoenix Contact AXC F 3152

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Phoenix Contact AXC F 3152 and is the answer not in the manual?

Phoenix Contact AXC F 3152 Specifications

General IconGeneral
BrandPhoenix Contact
ModelAXC F 3152
CategoryController
LanguageEnglish

Related product manuals