Operation
Operating Manual PSEN sc ME 5.5 08-17
1005388-EN-01
| 104
Serial numbers differ: On the display of the master unit, CFG NO MATCHING is shown.
Continue by selecting the data for the restoring.
Topology or MIB files vary: On the display of the master unit WAITING CONF is shown.
Continue the configuration in PSENscan Configurator.
3. Use the buttons on the display of the master unit to select the data to be used for
restoring.
Display master unit:
Restore cfg: The configuration in the memory module is used. Confirm the selection
with Confirm and the configuration is copied from the memory module into PSEN sc
ME 5.5 08-17. Continue checking the configuration.
cfg from GUI: The configuration created newly in the PSENscan Configurator is used.
Confirm your selection with Confirm and continue with Create new configuration in
PSENscan Configurator.
4. Display master unit: Confirm / Cancel
Display slave unit: CHECK MASTER
Confirm your entry with Confirm
5. Checking the configuration
Display master unit: RESTORE FAILED. Could not copy the configuration successfully.
Continue by selecting the data for the restore.
Display master unit: RUN TEST MODE
On the display of the master unit, select Enter Test. Test operation starts. Continue
with accept or reject configuration.
6. Accept or reject configuration
Test operation is complete.
Select Validate conf to accept the configuration. The safety laser scanner is ready for
operation again.
Select Reject conf to reject the configuration. Continue by selecting the data for the re-
store.
7. Create new configuration in PSENscan Configurator
Display master unit: WAITING CONF
Display slave unit: CHECK MASTER
Configure the safety laser scanner in PSENscan Configurator.
10.6 Reset
With the reset function, the safety laser scanner can be set to normal operation when the
safety laser scanner is in an error state, and the error was rectified.
Procedure:
Hold the reset pushbutton down for at least 500ms.