Project configuration
Operating Manual PSEN sc ME 5.5 08-17
1005388-EN-01
| 37
Applications of a reference outline for protecting additional protective equipment
When the reference points are set to the positions of additional protective equipment, for
example mechanical barriers, the safety laser scanner switches the OSSDs to the OFF
state when one of the marked positions changes.
[2]
[3]
[1]
[4]
[4]
[4]
[8] [8] [8]
[7]
[7]
[7]
[5]
[6]
Fig.: Using a reference outline for protecting additional protective equipment
Legend
[1] Danger zone
[2] Area covered by the safety laser scanner
[3] Safety laser scanner
[4] Reference points at protective equipment 1
[5] Additional protective equipment 1 that is protected by the reference points
[6] Additional protective equipment 2 that is protected by reference points
[7] Reference points at protective equipment 2
[8] Reference points on the floor
5.5 Area with limited detection capability
In the area of max.100mm before the laser scanner there is an areas with limited detec-
tion capability.
Please note:
} Ensure that the area is not part of the danger zone.
} Install the safety laser scanner so that no objects can enter the zone with limited detec-
tion capability.