Wiring
Operating Manual PSEN sc ME 5.5 08-17
1005388-EN-01
| 54
6 Wiring
6.1 General guidelines
} Information given in the Technical details [ 115] must be followed.
} Do not lay the connecting cable near or in contact with cables that carry high or highly
volatile currents.
} Use separate cables to connect the wires to the OSSDs of different safety laser scanners
or safety switches.
} For supply voltage, use only PELV/SELV power supplies that have a voltage buffer in ac-
cordance with EN60204-1.
} The protection type (see Technical details [ 115]) can only be achieved by using the
Pilz connection leads available as an accessory.
} Connection to evaluation devices
– Use the cables listed in the order reference (see Order references for
accessories [ 123]) or equivalent cables.
– The terminals for connection to the evaluation device must be kept in a lockable con-
trol cabinet. This prevents unauthorised modifications.
} Ensure compliance with permissible cable bending radii (see Technical details [ 115]).
} Do not connect outputs with test pulses to the inputs of the safety laser scanner.
6.2 Connector assignment master unit
The safety laser scanner PSEN sc ME 5.5 08-17 has configurable inputs and outputs. In
PSENscan Configurator these can be configured for the specific application.
The safety laser scanner PSEN sc ME 5.5 08-17 has an 8-pin male connector and a 17-pin
male connector for connection to the evaluation device and the supply voltage.
Use one of the two male connectors or both. The selected use has to be specified in
PSENscan Configurator.
Max. number Connection to
8-pin male con-
nector
17-pin male con-
nector
8-pin male con-
nector +
17-pin male con-
nector
OSSD pairs 1 3 3
Configurable inputs 2 4 8
Configurable outputs - 2 2
Configurable inputs/
outputs
1 2 2
Zone sets 3 20 70