Project configuration
Operating Manual PSEN sc ME 5.5 08-17
1005388-EN-01
| 51
Muting in one direction
Fig.: Distances between muting sensors - 2 muting sensors
Legend
[1] Safety laser scanner
A1 First muting sensor
B1 Second muting sensor
Icon Unit Minimum
value
Maximum value Description
L cm D
MutingOff
Length of the object that trig-
gers the muting status as it
passes the muting sensors
V cm/s 4.125 250 Speed at which the object is
moving
D
A-B
cm <D
MutingOff
Distance must be
covered within4s
Distance between the mut-
ing sensors A1 and B1
D
MutingOff
cm L Distance between muting
sensor A1 and the position
from which the muting func-
tion is turned off again
Distances for muting with 2 sensors
5.15.4 Dynamic muting
When Activate muting is selected for an input, muting can be activated and deactivated
dynamically.
} Conditions for the occurrence of muting
– One of the inputs 3, 9, 10 or 11 is connected to a controller and it receives a high sig-
nal from there when muting is to be activated
– When configuring the inputs, Activate muting is configured for this input in
PSENscan Configurator
– the first sensor has detected conveyed material and the second sensor also detected
it max.4s afterwards