Project configuration
Operating Manual PSEN sc ME 5.5 08-17
1005388-EN-01
| 51
Muting in one direction
A1B1
[1]
D
A-B
D
MutingOff
L
V
Fig.: Distances between muting sensors - 2 muting sensors
Legend
[1] Safety laser scanner
A1 First muting sensor
B1 Second muting sensor
Icon Unit Minimum
value
Maximum value Description
L cm D
MutingOff
Length of the object that trig-
gers the muting status as it
passes the muting sensors
V cm/s 4.125 250 Speed at which the object is
moving
D
A-B
cm <D
MutingOff
Distance must be
covered within4s
Distance between the mut-
ing sensors A1 and B1
D
MutingOff
cm L Distance between muting
sensor A1 and the position
from which the muting func-
tion is turned off again
Distances for muting with 2 sensors
5.15.4 Dynamic muting
When Activate muting is selected for an input, muting can be activated and deactivated
dynamically.
} Conditions for the occurrence of muting
One of the inputs 3, 9, 10 or 11 is connected to a controller and it receives a high sig-
nal from there when muting is to be activated
When configuring the inputs, Activate muting is configured for this input in
PSENscan Configurator
the first sensor has detected conveyed material and the second sensor also detected
it max.4s afterwards