12--2
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 Rev . N 013004
12.4 System Event Messages
When a system event occurs, a message appears on the LCD screen in the UPS
Status area. This message is also is written to the Active Events log and may be
added to the Events History Log. The messages are divided into four categories:
Alarms, Notices, Status, and Commands. The following tables contain the events
displayed on the LCD System Events screen of the Control panel.
ALARMS
Message Horn Phone Relay Log Indication
Battery Over Voltage 1 No 1 HA Service Required
Battery Over Voltage OK Off No 1 HA Condition Cleared
Battery Time is Low 1 No 1 HA User Action Required
Battery Time is Low OK Off No 1 HA Condition Cleared
Battery Under Voltage 1 No 1 HA Shutdown Imminent
Battery Under Voltage OK Off No 1 HA Condition Cleared
Bypass Calibration Required 1 No 1 HA Service Required
Bypass Calibration Required OK Off No 1 HA Condition Cleared
Bypass Control Failure 1 4 1 A Service Required
Bypass Overheating Shutdown 1 No 1 HA User Action Required
Bypass Overheating Shutdown OK Off No 1 HA Condition Cleared
Bypass Overheating Warning 1 No 1 HA Shutdown Imminent
Bypass Overheating Warning OK Off No 1 HA Condition Cleared
Bypass Phase Rotation 1 No 1 HA User Action Required
Bypass Phase Rotation OK Off No 1 HA Condition Cleared
Bypass Setup Required 1 No 1 HA Service Required
BypassSetupRequiredOK Off No 1 HA Condition Cleared
Calibrate DC AutoBalance 1 4 1 HA Service Required
Calibrate DC AutoBalance OK Off No 1 HA Condition Cleared
Charger Failure 1 4 1 HA Service Required
Charger Failure OK Off No 1 HA Condition Cleared
Check Battery 1 No 1 HA User Action Required
Check Battery OK Off No 1 HA Condition Cleared
Check Boost 1 4 1 HA Service Required
Check Boost OK Off No 1 HA Condition Cleared
Check CSB Setup 1 No 1 HA Service Required
Check CSB Setup OK Off No 1 HA Condition Cleared
Check Inverter 1 No 1 HA Service Required
Check Inverter OK Off No 1 HA Condition Cleared