Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 Rev . N 013004
3.5 Installing and Connecting Remote Battery
System
Install and connect remote Battery System as follows:
CAUTION:
When sizing battery system, do not exceed internal battery charger capabilities.
Refer to Chapter 15 “Specifications”, for maximum battery charger currents.
1. Install battery system in accordance with battery and rack manufactures
instructions.
2. Install DC disconnect device between battery system and UPS Cabinet.
3. Connect battery system to UPS cabinets (refer to Paragraph 2.2.4 or 2.4.3).