Installing the UPS System
2.1 Preliminary Installation Information
WARNING:
Installation should be performed only by qualified personnel.
Refer to the following while installing the UPS system:
• Refer to Appendix A of this manual for installation drawings and additional
installation notes.
• Dimensions in this manual are in millimeters and inches.
• Do not tilt the cabinets more than 10˚ during installation.
• The conduit landing plates are to be removed to add conduit landing holes as
required. Plate material is 16 gauge steel (0.060 in. thick).
• The cabinets must be installed on a level floor suitable for computer or
electronic equipment.
• If perforated floor tiles are required for ventilation, place them in front of the
UPS. Refer to Table AA in Appendix A for equipment weight and point loading.
• Proper UPS operation requires a Bypass Input Neutral connection. This neutral
is required to be the common conductor between all bypass source phases
(e.g., ”wye” or ”4-wire” source).
• Details about control wiring are provided in each procedure for connecting
options and features. Drawing 164201300---2 and Tables X and Y in Appendix A
identify the control wiring terminations.