15--3
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 Rev . N 013004
15.4 Environmental Specifications
Operating Temperature 0to40˚C without derating. The recommended
operating temperature is 25˚C.
Operating Altitude Maximum 1500m (5000 ft) at 40_C without
derating
Storage Temperature --- 2 0 t o + 7 0 ˚C (prolonged storage above 40˚C
will cause rapid battery self-discharge)
Relative Humidity (operating and
storage)
95% maximum, noncondensing
Acoustical Noise 60 dBA at a 1m distance (Typical)
EMI Suppression Meets FCC Regulation 47, Part 15, for class A
devices
Electrostatic Discharge (ESD)
Immunity
Meets IEC 801---2 specifications. Withstands up
to 25 kV pulse without damage and with no
disturbance or adverse effect to the critical load.