EasyManua.ls Logo

Powerware 9330 - UPS Circuit Breakers; Smart LOAD off; Maintenance Bypass Switch; Cold Start Switch

Powerware 9330
268 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8-- 4
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 Rev . N 013004
8.2.2 UPS Circuit Breakers
The UPS can contain as many as 10 circuit breakers, depending on the system
options. The UPS circuit breakers are described in detail in Chapter 10, UPS
Operating Instructions.”
UPS Cabinet
CB1 controls the input t o the UPS rectifier, while CB2 controls the battery input to the
UPS inverter. CB1 and CB2 are manually controlled.
Optional Battery Cabinet
A local battery circuit breaker controls the output of each battery cabinet, providing
the ability to service each battery string individually.
Optional Options Cabinet
Input, output, and bypass circuit breakers control the flow of current to and from the
installed transformers.
8.2.3 Smart LOAD OFF
AsmartLOAD OFF pushbutton is provided for situations where you must quickly
control the UPS output. The pushbutton is located on the front of the UPS for
quick access, but provides a safety feature to prevent inadvertent load dumps. The
LOAD OFF pushbutton is described in detail in Chapter 10, “UPS Operating
Instructions.”
8.2.4 Maintenance Bypass Switch
An internal Maintenance Bypass switch is provided to completely isolate the main
power processing unit of the UPS during service. The Maintenance Bypass
Switch is described in detail in Chapter 10, “UPS Operating Instructions.”
8.2.5 Cold Start Switch
A Cold Start switch is provided to start the UPS in Battery Mode when no
commercial power is available. The Cold Start Switch is described in detail in
Chapter 9, “UPS Operating Instructions.

Table of Contents

Other manuals for Powerware 9330

Related product manuals