5-- 2
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 Rev . N 013004
5.2 To i n s t a l l a n R M P :
NOTE: If mounting to a hollow wall, secure the enclosure bottom to a wood or metal
stud within the wall. Do not use hollow wall anchors. The RMP also has
provisions to be mounted to a single or double gang wall electrical box.
1. Be sure the UPS system is turned off and all power sources are removed.
(See the operation section of this manual for shutdown instructions.)
2. If wall mounting, securely mount the RMP. If desk mounting, install provided
bumpers to the bottom of the RMP enclosure.
3. Install the Industrial Relay Card (IRC) into an open X-Slot on the rear panel of
the UPS Cabinet. Remove X-Slot cover panel to gain access to the X-Slot.
4. If wall mounting, proceed to step 5; if desk mounting, proceed to step 6.
5. Install wiring from the RMP to the UPS using ½-in. conduit through the cable
exit openings in the IRC (see Figure 5---2) and the RMP (refer to Drawing
164201300---19 in Appendix A). Proceed to step 7.
6. Install wiring from the RMP to the UPS using cable listed in Table 5---1 and
provided strain relief bushings in the cable exit openings in the IRC (see Figure
5---2) and the RMP (refer to Drawing 164201300---19 in Appendix A).
7. Connect wiring between the RMP and the UPS IRC plug-in terminal blocks
using terminations shown in Table 5---1. See Figures 5---2 and 5---3 for plug-in
terminal block locations.
Table5---1. RMPWireTerminations
From RMP To UPS IRC Remarks
J 1 --- 1
J 1 --- 1
J 1 --- 3
J 1 --- 3
U
B
l
d
8
6
9
0
0
6
0
J 1 --- 4
J 1 --- 4
Use Belden 8690 060
r
e
q
u
i
v
a
l
e
n
t
C
a
b
l
e
J 1 --- 5
J 1 --- 5
r
e
q
u
i
v
a
l
e
n
t
C
a
b
l
e
J 1 --- 6
J 1 --- 6
8. To check the operation of the RMP, ensure that the UPS system is supplying
the load via the inverter or bypass. If the indicators on the RMP show the
appropriate status, then it is operating correctly.
If the RMP is not operating correctly, check the wiring, the fuse on the IRC, and
the plug-in terminal blocks for proper seating. If all connections are secure but
the RMP still does not operate correctly, replace the fuse. If this does not
correct the problem, contact your local field service office for verification that
the RMP is working correctly.