EasyManua.ls Logo

Powerware 9330 - Warranty

Powerware 9330
268 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DESCRIPTION:
DATE:
DRAWING NO:
1of17
SHEET:
REVI SION:
N
NOTE:
Callout letter
and
map to drawing #164201300---6
,,,
013004
A
B
C
D
164201300---1
POWER WIRING INSTALLATION NOTES
A --- 2
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 Rev . N 013004
Table A. INPUT/OUTPUT Ratings & External Wiring Requirements for
Po werw are 9330---20/10
(Without Options Cabinet)
Ratings
Units Rating 50/60 Hz
Basic unit ratings at
0.7 lagging PF load
KVA
KW
10
7
10
7
g
g
g
INPUT/OUTPUT
VOLTAGE
208 220
A
CIn
p
ut to UPS Rectifier
(
0.95min.PF
)
A
m
p
s
*
2
8
2
7
A
C
A
C
I
n
p
u
t
t
o
U
P
S
R
e
c
t
i
f
i
e
r
(
0
.
9
5
m
i
n
.
P
F
)
3,1gnd
A
mps* 28 27
A
INPUT
3
,
1
g
n
d
Minimum conductor size (number per )
AWG or kcmil(ea) 8(1) 8(1)
*(Maximum amps includes full load current plus
battery recharge current)
A
C
AC Input to Module Bypass (UPS Bypass)
Full Loa
d
Cu
r
r
en
t
3
,
(
1
)
Neut
r
al
,
(
1
)
g
n
d
Amps
27.8 26.3
A
INPUT
F
u
l
l
L
o
a
d
C
u
r
r
e
n
t
3
,
(
1
)
N
e
u
t
r
a
l
,
(
1
)
g
n
d
Minimum conductor size (number per )
AWG or kcmil(ea) 8(1) 8(1)
DC
I
P
U
T
DC Input from External Battery Source to UPS
(1) positive, (1) negative, (1) gnd
VDC (Nominal)
Amps
288
26
288
26
INPUT
(
)
p
,
(
)
g
,
(
)
g
Minimum conductor size (number per pole) (See note 8)
AWG or kcmil(ea) 8(1) 8(1)
A
C
AC Output to Critical Load
F
u
l
l
L
o
a
d
C
u
r
r
e
n
t
3
(
1
)
N
e
u
t
r
a
l
(
1
)
g
n
d
Amps 27.8 26.3
A
OUTPUT
F
ull Loa
d
Cu
r
r
e
n
t3,
(
1) Neut
r
al,
(
1) g
n
d
Minimum conductor size (number per )
AWG or kcmil(ea) 8(1) 8(1)
Read and understand the following notes while planning your installation:
1. Refer to national and local electrical codes for acceptable external wiring practices.
2. The bypass feed into this equipment utilizes four wires. The rectifier feed into this
equipment utilizes three wires. However, the phases must be symmetrical about ground
(i.e., from a Wye source) for proper equipment operation. Failure to follow these
instructions will void the product warranty.
3. Material and labor for external wiring requirements are to be provided by designated
personnel.
4. For external wiring, use 90°C copper wire. See the appropriate column in Tables A
through M.
5. Wire ampacities are chosen from Table 310---16 of the NEC.
6. A bypass neutral feeder must be supplied.
7. Refer to Section I of this manual for installation Instructions.
8. UPS systems not using an external battery source are supplied with internal batteries
prewired to the UPS at the factory. External Line-up and Match Battery cabinets are
provided with with quick disconnect cables for connection to the UPS. No external wiring
is required for Line-up and Match battery cabinets. All products can be connected to an
external battery source through the DC connections terminal block. An external DC
ground is established through the grounding terminal in the bottom of the cabinet.

Table of Contents

Other manuals for Powerware 9330

Related product manuals