12--4
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 Rev . N 013004
ALARMS
Message IndicationLogRelayPhoneHorn
Input Failure 1 4 1 HA Service Required
Input Failure O K Off No 1 HA Condition Cleared
Input Phase Rotation 1 No 1 HA User Action Required
Input Phase Rotation OK Off No 1 HA Condition Cleared
Inverter DC Link OV 1 No 1 HA Service Required
Inverter DC Link OV OK Off No 1 HA Condition Cleared
Inverter DC Link UV 1 No 1 HA Service Required
Inverter DC Link UV OK Off No 1 HA Condition Cleared
Inverter Not Responding 2 No 1 HA Service Required
Inverter Not Responding OK Off No 1 HA Condition Cleared
Inverter Overheating Shutdown 1 No 1 HA User Action Required
Inverter Overheating Shutdown OK Off No 1 HA Condition Cleared
Inverter Overheating Warning 1 No 1 HA Shutdown Imminent
Inverter Overheating Warning OK Off No 1 HA Condition Cleared
Inverter Overload 1 No 1 HA User Action Required
Inverter Setup Required 1 No 1 A Service Required
Inverter Tripped 1 No 1 A User Action Required
Inverter Voltage Failure 1 4 1 HA Service Required
Inverter Voltage Failure OK Off No 1 HA Condition Cleared
Load Over 100% 1 No 1 HA Shutdown Imminent
Load Over 100% OK Off No 1 HA Condition Cleared
Load Over 125% 1 No 1 HA Shutdown Imminent
Load Over 125% OK Off No 1 HA Condition Cleared
MCU Calibration Required 1 No 1 HA Service Required
MCU Calibration Required OK Off No 1 HA Condition Cleared
MCU Setup Required 1 No 1 HA Service Required
MCU Setup Required OK Off No 1 HA Condition Cleared
MCU Not Responding 1 No 1 HA Service Required
MCU Not Responding OK Off No 1 HA Condition Cleared
Not Enough UPMs 1 No 1 HA User Action Required
Not Enough UPMs OK Off No 1 HA Condition Cleared
Output Overload 100% 1 No 1 HA User Action Required
Output Overload 100% OK Off No 1 HA Condition Cleared
Output Overload 125% 1 No 1 HA User Action Required
Output Overload 125% OK Off No 1 HA Condition Cleared
Output Phase Rotatio n 1 No 1 HA User Action Required
Output Phase Rotatio n OK Off No 1 HA Condition Cleared
Parallel Setup Error 1 4 1 A Service Required
Parallel Setup Error OK Off No 1 A Condition Cleared