12--9
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 Rev . N 013004
STATUS
Message Horn Phone Relay Log Indication
Alarm Lamp No No 1 No Service Status
Auto Mode No No No A User Status
Bypass is Available No No No A User Status
Charger On No No No HA Service Status
Charger Off No No No HA Service Status
CSB Power Supply on No No No A Service Status
H i --- E f f M o d e No No No No User Status
Inverter O n No No No HA Service Status
Inverter O ff No No No HA Service Status
Inverter Under Voltage 1 No No HA Service Status
Inverter Under Voltage OK Off No No HA Service Status
K1 (Input) Closed No No No HA Service Status
K1 (Input) Open No No No HA Service Status
K2 (Battery) Closed No No No HA Service Status
K2 (Battery) Open No No No HA Service Status
K3 (Inverter) Closed No No No HA Service Status
K3 (Inverter) Open No No No HA Service Status
K5 (Backfeed) Closed No No No HA Service Status
K5 (Backfeed) Open No No No HA Service Status
Modem OK No No No A User Status
Notice Lamp No No 2 No Service Status
On Battery No No No A User Status
On Bypass No No No A User Status
PPU Shutdown No No No A User Status
SBM Bypass No No No A User Status
Unit Normal No No No A User Status
UPS Power Supply No No No HA Service Status
UPS Power Supply OK No No No HA Service Status
Table Key To Log Column
HA --- Event recorded in History and Active Logs.
A --- Event recorded in Active Log only.