13--14
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 Rev . N 013004
Inverter Version 0.97
Machine Control Version 0.99
Comm Server Version 0.98
Display Version 0.96
08/11/2000 14:13:03.000 STATUS: CSB Power Supply On
08/11/2000 14: 13:03.043 NOTICE: Inverter Initializing
08/11/2000 14:13:05.721 STATUS: UPS Power Supply OK
08/11/2000 14:13:05.728 NOTICE : Input Under Voltage
08/11/2000 14:13:05.729 NOTICE : Output Under Voltage
08/11/2000 14:13:05.729 NOTICE : Bypass Under Voltage
08/11/2000 14:13:05.749 AL ARM: Rectifier Under Voltage
08/11/2000 14:13:10.459 AL ARM: Batt ery Under Volt age
08/11/2000 14:13:12.954 NOTICE : Battery Voltage Low
08/11/2000 14:13:13.165 NOTICE : Battery Not Present
08/11/2000 14:13:34.710 STATUS: PPU Shutdown
08/11/2000 14:13:57.773 NOTICE : Check Modem
08/11/2000 14:14:33.520 AL ARM: Inverter Tripped
08/11/2000 14:14:33.520 AL ARM: Check Inverter
08/11/2000 14:27:09.000 STATUS: CSB Power Supply On
08/11/2000 14: 27:09.043 NOTICE: Inverter Initializing
08/11/2000 14:27:11.725 STATUS: UPS Power Supply OK
08/11/2000 14:27:11.733 NOTICE: Input Under Voltage
08/11/2000 14:27:11.733 NOTICE: Output Under Voltage
08/11/2000 14:27:11.733 NOTICE: Bypass Under Voltage
08/11/2000 14:27:11.754 ALARM: Rectifier Under Voltage
08/11/2000 14:27:16.464 AL ARM: Battery Under Voltage
08/11/2000 14:27:18.954 NOTICE : Battery Voltage Low
08/11/2000 14:27:19.169 NOTICE : Battery Not Present
08/11/2000 14:27:40.714 STATUS: PPU Shutdown
08/11/2000 14:28:04.023 NOTICE : Check Modem
08/12/2000 14:15:09.000 STATUS: CSB Power Supply On
08/12/2000 14:15:09.043 NOTICE: Inverter Initializing
08/12/2000 14:15:11.725 STATUS: UPS Power Supply OK
08/12/2000 14:15:11.733 NOTICE : Input Under Voltage
08/12/2000 14:15:11.733 NOTICE : Output Under Voltage
08/12/2000 14:15:11.754 AL ARM: Rectifier Under Voltage
08/12/2000 14:15:11.833 NOTICE : Maintenance Bypass On
08/12/2000 14:15:16.463 ALARM: Bat tery Under Vol tage
08/12/2000 14:15:18.954 NOTICE: Battery Voltage Low
08/12/2000 14:15:19.169 NOTICE: Battery Not Present
08/12/2000 14:15:40.714 STATUS: PPU Shutdown
08/12/2000 14:16:04.023 NOTICE: Check Modem
08/12/2000 14:16:22.925 CMD: Bypass Mode Command
08/12/2000 14:16:23.443 STATUS: K5 (Backfeed) Closed
08/12/2000 14:16:23.586 STATUS: On Bypass
08/12/2000 14:16:24.860 NOTICE: Output Under Voltage OK
08/12/2000 14:17:20.900 NOTICE: Input Under Voltage OK
08/12/2000 14:17:23.606 ALARM: Rec tifier Under Voltage OK
08/12/2000 14:17:25.557 ALARM: Bat tery Under Vol tage OK
08/12/2000 14:19:01.899 CMD: PPU On Command
08/12/2000 14:19:04.089 STATUS: K1 (Input) Closed
Figure 13---19. Event History Log