AFV
+
Series High Power Programmable AC Power Supply
5-101
5.5.5 Step Mode
Setup Group1 Parameters:02 10 01 05 00 06 0C 00 01 08 98 01 F4 00 00 00 00
00 0A 66 84(hex)
Setup Running Cycle Parameters:02 10 01 0b 00 03 06 00 01 00 18 00 01 EA 5D
(hex)
Run Step Mode:02 06 00 01 00 02 59 F8(hex)
Note1
:
All the voltage&Frequency value here: Real Value x 10
Note2
:
The blue hex data above is the group no.
5.5.6 Gradual Mode
Setup Group1 Parameters:02 10 01 0e 00 08 10 00 01 08 98 01 F4 04 4C 02 58
00 00 00 00 00 0A 34 FA(hex)
Setup Running Cycle Parameters:02 10 01 16 00 03 06 00 01 00 0C 00 01 71 A3
(hex)
Run Gradual Mode:02 06 00 01 00 03 98 38(hex)
Note1
:
All the voltage&Frequency value here: Real Value x 10
Note2
:
The blue hex data above is the group no.
5.5.7 Output Status
System error & output status:02 03 02 02 00 17 A5 8F (hex)
Note
:
All the voltage&Frequency value here: Real Value x 10
5.5.8 Stop
02 06 00 01 00 00 D8 39(hex)
5.5.9 Reset
02 06 00 01 00 20 D9 E1(hex)