Series High Power Programmable AC Power Supply
2-28
Figure 2.8 AFV
+
Output Cable Size Chart
*The ambient temperature should be below 35℃, and the temperature rating of conductor
insulation for wires should be at least 60℃.
Figure 2.9 Current Rating of AWG
The tables above give minimum recommended cable size; these recommendations
are for multi core flexible copper cables and are for reference only. The user can
select different cables according to the actual input and output conditions. When
the length of cable is more than 20 meters, the cable gauge should be doubled.