Prontonet User’s Manual v410 85
V.3 Alarms
The alarm window allows to select the alarms that the unit will check. The unit
will notify the occurrence of each of the selected alarms. It is possible to
configure the unit to send SNMP traps to notify alarms information. See chapter
V.1.1.5.
V.3.1 Selecting Alarms
The unit allows many different alarms. The selection menu is opened by clicking
over the Alarm area.
Voltage Out of Range 12 v Main: The voltage from the main power supply
(AC/DC) is out of range.
Voltage Out of Range 12 v Backup: The voltage from the backup power
supply is out of range.
Voltage Out of Range 3.3 v System: The voltage from the 3.3 DC/DC
converter is out of range.
Voltage Out of Range 5 v System: The voltage from the 5 DC/DC
converter is out of range.
Temperature Out of Range: The temperature is out of range
Fan Failure: The fun is activated if the internal temperature is over 35º. The
Fan Failure alarm will be activated if the fun doesn’t work when the
temperature is over this threshold.
LAN NOT Present: Not physical level detected in the LAN port.
LAN Traffic: The LAN traffic is higher than the 90% of the capacity of the
network.