MODELS
USER GUIDE
GETTING STARTED
SMART-SPACE CONTROLLER
UNIVERSAL INPUT RANGES
Universal inputs are configured with analog or binary ranges using RC-Studio.
REAL TIME CLOCK
Models with the Real Time Clock option come with a 72-hour backup capacitor. By default,
Jumper 10 (J10) is connected as shown in Figure 5. This jumper (also labelled Clear
memory) connects the 72-hour backup capacitor to the SMART-Space Controller circuitry.
By unplugging J10 (and with no external power applied) volatile memory contents, date,
and time will be cleared. The memory content that would be lost includes:
Trend data (logs and runtime),
Calculated variable values, and
Calculated output values.
Jumper 10 must be installed for the capacitor power backup to function. Failure to install
Jumper 10 will result in data loss in the event of a power failure.