UNIVERSAL INPUT RANGES
Universal inputs are configured with analog or binary ranges using RC-Studio.
REAL TIME CLOCK
Models with the Real Time Clock option come with a 72-hour backup capacitor. By default,
Jumper 10 (J10) is connected as shown in Figure 5. This jumper (also labelled Clear
memory) connects the 72-hour backup capacitor to the SMART-Space Controller circuitry.
By unplugging J10 (and with no external power applied) volatile memory contents, date,
and time will be cleared. The memory content that would be lost includes:
• Trend data (logs and runtime),
• Calculated variable values, and
• Calculated output values.
Jumper 10 must be installed for the capacitor power backup to function. Failure to install
Jumper 10 will result in data loss in the event of a power failure.