DISPLAY CONFIGURATION
84
2012-2015 Reliable Controls Corporation
TIME EDITING
The Real Time Clock can be displayed on and edited from the LCD interface of the SSC.
TO ENABLE THE DISPLAY OF THE REAL TIME CLOCK ON THE SSC’S LCD
1 Select the BACnet tab in RC-Studio.
2 Open the Display Configuration worksheet.
FIGURE 76:DISPLAY CONFIGURATION IN RC-STUDIO
3 Enter a name in the Display Name column such as Time.
4 In the Point column, enter [0]0.
5 The Type column must be set to Analog and the Range column must be set to
Time.
6 Click the Mode button or press the F10 key to save the changes.
The second point in the Display Configuration worksheet is often used as a “quick
adjust” and is typically the room temperature setpoint. It is recommended the time point be
configured to use point 3 or higher to avoid accidental time changes.