EasyManua.ls Logo

Rockwell Automation Allen-Bradley PowerMonitor 5000 Unit - Page 195

Rockwell Automation Allen-Bradley PowerMonitor 5000 Unit
514 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 195
Logic Functions Chapter 7
Operation
•AND
An AND gate output asserts when ALL of its enabled inputs are asserted.
Disabled inputs are ignored. If only one input is enabled, the logic gate
output copies the input state.
•NAND
A NAND, or Not-AND, gate output asserts except when ALL of its
enabled inputs are asserted. Disabled inputs are ignored. If only one input
is enabled, the logic gate output inverts the input state.
•OR
An OR gate output asserts when ANY of its enabled inputs is asserted.
Disabled inputs are ignored. If only one input is enabled, the logic gate
output copies the input state.
•NOR
A NOR, or Not-OR, gate asserts when NONE of its enabled inputs are
asserted. Disabled inputs are ignored. If only one input is enabled, the logic
gate output inverts the input state.
•XOR
An XOR, or exclusive-OR, gate asserts when only one of its two inputs is
asserted. An XOR gate must have two and only two inputs enabled. Both
inputs must be configured simultaneously or an error results.
•XNOR
An XNOR, or exclusive-NOR, gate asserts when either both of its two
inputs are asserted or both are de-asserted. An XNOR gate must have two
and only two inputs enabled. Both inputs must be configured
simultaneously or an error results.
In general, a logic gate is disabled and its output is de-asserted if none of its inputs
are enabled. Except for XOR and XNOR gates, any combination of enabled and
disabled inputs is accepted. The output of a logic gate is not permitted to be used
as the input to a logic gate.
Setpoint Setup
The tags that are listed in this section configure the operation of each setpoint,
and are found in the Configuration.Setpoints_1_5
and
Configuration.Setpoints_6_10
tables in the M5 model. The M6 and M8 models
also have two additional tables for setting up setpoints,
Configuration.Setpoints_11_15 Data Table
and
Configuration.Setpoints_16_20 Data Table
, and a Relative_Setpoint_Interval
tag in the Configuration.PowerQuality
table for configuring the sliding reference
for all setpoints. These tables are in Appendix A
.

Table of Contents

Related product manuals