64 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Chapter 3 Setup and Commands
13. Set the Connection and Configured By selections to the appropriate
settings for your application.
See
Controller Applications: Class 1 Connection on page 242 for more
information.
In this example, the Connection and Configured By fields are left at the
default selections of Data and This Controller.
14. To save and close the Module Definition dialog box, click OK.
15. If prompted, click Yes to change the module definition.
IMPORTANT The default module definition settings for 1426-MxE catalog numbers
automatically enables Automatic Device Configuration. When a connection
is established, the controller overwrites any existing configuration settings
of the PowerMonitor 5000 unit. If you do not wish to allow automatic
delivery of the configuration instance by the controller, set the Connection to
Data and Configured By to External Means.
IMPORTANT Catalog numbers that end in -CNT or -DNT are only permitted to have an
Input Only connection type.