Reference Manual
00809-0100-4664, Rev BA
January 2010
Rosemount 8712
E-26
Series 9100A/9200A
Sensors to 8712
Transmitter
Connect coil drive and electrode cables as shown in Figure E-24.
Figure E-24. Wiring Diagram for
Foxboro Series 9100A/9200A
and Rosemount 8712
Table E-22. Foxboro Series 9100A/9200A Sensor Wiring Connections
Rosemount 8712
Foxboro
Series 9100A/9200A Sensors
11
2 2
Chassis Ground
17 Chassis Ground
18 White (W)
19 Black (B)
B
W
1
2
FOXBORO SERIES
8000A/9300A SENSOR
ROSEMOUNT 8712
TRANSMITTER
This is a pulsed DC magnetic flowmeter.
Do not connect AC power to the sensor
or to terminals 1 and 2 of the
transmitter, or replacement of the
electronics board will be necessary.