Features and Concepts
Page 19 AC-115 Hardware Installation and User's Guide
3.4 Events and Event Actions
All of the AC-115’s key features are triggered by some events.
For instance, placing a valid code at the reader at the right
time is an Event, and the Valid Code Event may trigger the
Lock Strike Output to activate an Event Action.
In this section, you will learn about the AC-115’s Events and the
Event Actions those Events cause.
Monitor Event
The Monitor Event is triggered when the Door Monitor Switch
has been activated, i.e. the door has been opened.
Possible Monitor Event Actions
Chime Alert
Door Ajar Event if door is not closed in time
Forced Door Event if valid code was not entered
Door Ajar Event
A door is considered ajar when the Door Monitor Switch has
been activated with a Valid Code being entered. If the door is
left open longer than the Ajar Delay Time, a Door Ajar Event
will occur.
Possible Ajar Door Event Actions
Siren Event (Programmable Siren Time)
Auxiliary Output Activation (Programmable Auxiliary
Release Time)
Forced Door Event
A door is considered forced open when the Door Monitor
Switch has been activated without a Valid Code being
entered. When this occurs, a Forced Door Delay Time will count
down. When the count is done, the Forced Door Event will
occur.