SYSTEM PARAMETERS—SERVICE LEVEL 2 PARAMETERS
36
P. 9 4 0 Volt Input voltage
(The real time voltage the board is receiving. Electrical meters
measure the voltage as an RMS or essentially an average;
therefore, an electrical meter reading may vary by 20 volts or
more. P:940 displays the voltage in real time. If the control
board receives a voltage greater than 10%, its rating error
F:525 will appear until the voltage drops back down within
acceptable range. If this continues, a line reactor will be
needed to prevent the failure. When incoming power is
ungrounded, an isolation transformer may be needed. (Part
number for the Line reactor is 0011748 and the isolation trans-
former is part number 00111101.)
P. 9 8 0 0–5 Operating mode
(This parameter is used to set the operating mode for the con-
troller)
The following modes are possible:
0: Door travels in automatic mode.
1: Door opens in automatic, closes in manual (jog) mode.
2: Door travels in jog mode open and close.
3: Jog mode only (deadman) emergency operation; and no
safety inputs required for deadman operation.
All safety devices and limit switches are ignored.
4: Endurance test with safety devices automatic OPEN and
CLOSE operation. Before each new operation the hold-open
time P.010 is in effect
5: Endurance test without safety devices
All safety devices are ignored.
NOTE: The endurance test setting is lost after turning off
the controller. The controller then reverts to man-
ual mode.
0
P. 9 8 5 0–3 Text language
0: English text
1: German text
2: Spanish text
3: French text
0
P. 9 9 9 Password (for accessing Service Levels 2) is the number 10
P. F 0 0 0–1 Activation of the wireless
(Activate the functions of the wireless in the controller)
Parameter Range Service Level 2 Parameters
Factory
Setting