A.2
Appendix A
Figure A-2: SALUS AKL06PRF Zone Pump Wiring Center
- Domestic Hot Water (DHW) Priority controlled by boiler (Priority Dip Switch – O )
- 6 Central Heating (CH) Zones
- Boiler CH pump output enables/disables heating zones
LN
POWER IN
120 VAC
GROUND
GROUND
LN
PRIORITY
PUMP 1
LN
PUMP 2
LN
PUMP 3
LN
PUMP 4
LN
PUMP 5
LN
PUMP 6
LN
PRIMARY
PUMP
120 VAC OUTPUT
ZC
N
OFF
WIRELESS
SLAVE
OFF
EXERCISE ON
MASTER
PRIORITY ON
PRIMARY STATUS DURING PRIORITY ON
WIRED
OFF
OFF
PURGE ON
AUX XX
ZONE1
E/S
H N
R
C
W
24V - T-STAT 1
CH DEMAND
DHW DEMAND
BOILER
BOILER PUMP
STAT
INDIRECT
DHW
AKL06PRF
6 ZONE PUMP WIRING
CENTER
1
2
3
4
5
6 CENTRAL HEATING (CH) ZONES
DHW PUMP
6
CH PUMP
DHW PRIORITY
(SEE NOTE 1)
THIS DOCUMENT CONTAINS
INFORMATION PROPRIETARY
TO AZ ENGINEERING.
DISCLOSURE OF ANY
INFORMATION CONVEYED OR
IMPLIED BY THIS DOCUMENT
WITHOUT EXPRESS WRITTEN
CONSENT BY AZ
ENGINEERING IS FORBIDDEN.
APPROVED BY
DATE
AZ ENGINEERING LLC
AKL06PRF INSTALLATION SCHEMATIC
SCALE: DRAWING NO: REVISION:
SHEET 1 OF 1
DATE:DRAWN BY:
CN:
1 DHW ZONE: 6 CH ZONES
SCI-20180531-03 01
NONE
--
SCEARCE 2018-05-31
REVISION
BY:
1
DAS
DATE:
6/11/18
ADDED SYMBOL KEY & NOTES BLOCK, ADDED LABEL "DHW PRIORITY
(SEE NOTE 1)", ADDED "6 CENTRAL HEATING (CH) ZONES"
NOTES:
1) DHW PUMP IS CONTROLLED BY THE BOILER DHW OUTPUT
2) CH PUMP OUTPUT TO ZC/N ENABLES ZONES
3) ZONE 1 T-STAT MAY NOT BE WIRED, WIRELESS T-STAT ONLY
KEY:
WATER
ELECTRICAL
CONTROL BOUNDARY
ZONE CIRCULATOR