RestoringuserprogramandDB/text
Two options are available:
- With the Saia PG5
®
under
“Online→Flashmemory→Restoresourceofash”or
- By pressing the “Run/Stop” button for at least 3 - 5 seconds in RUN mode.
ATTENTION: If the button is pressed for longer than 10 seconds, there
is the risk of resetting the system and/or deleting the memory.
TheCPUsearchesmemorylocationsforbackuplesinthefollowingorder:
1. M1 Flash
2. INTFLASH
3. PLC_SYS