5 Commisioning
Operating instructions for actuators type AB with SMARTCON control unit
OM-ENGLISH-CSC-V2.08-2019.11.07
Figure 27 Figure 28
Then, push down the selector switch until it snaps into place. In doing so, the bottom right now on the display
will show "TEACHIN"
CAUTION: Once the display shows "TEACHIN", use the operating switch (black switch) to
start the motorised operation of the actuator. In this mode, no travel-dependent switch off
occurs in the end position.
CAUTION: Please note that, during motor operation, only torque monitoring remains active,
as travel adjustment will happen subsequently. Therefore, please check beforehand whether
the maximum torque has been already parameterised
Absolute and relative values on the display will change continuously along with position changes.
Figure 29
Figure 30
Manually move the actuator with the handwheel (see section 2.1, page 4 or 2.6, page 6) or by motor via the
operating switch (black button) to the end position OPEN of the valve.
• Absolute value: Absolute value of the position feedback
• Relative value: the value to the other end postion
Figure 31: 1. . . Absolute value, 2. . . Relative value
When the desired end position OPEN of the valve is reached, move the selector switch back to the middle
position. Thus, the line "TEACHIN" disappears.
Figure 32
Figure 33