7 Parameter menu
Operating instructions for actuators type AB with SMARTCON control unit
OM-ENGLISH-CSC-V2.08-2019.11.07
7.10 Parameter group: Position output (option)
Position output is used to indicate the current position of the actuator using 0/4-20 mA; it can retrofitted using
smartcode.
If this option is not enabled, the menu point shows the message "inactive".
No adjustment to the end positions or the travel is required. Adjustment is automatically performed during the
configuration of travel limit positions (see section 7.1, page 24)
No further settings are necessary for torque-dependent switch-off because the controller exclusively uses travel
limit positions for the calculation, regardless of whether this is defined by the torque or the travel limit positions.
The factory default setting is:
4 mA at 0% position 20 mA at 100% position
Menu item
Sub-Menu
item
Poss. setting Notes / comments
P11.1
Position-
Output
Function disabled Position Output disabled
enabled Position Output enabled
P11.2
Position-
Output
Start (at 0%)
0 20.5 mA
{4 mA}
mA value for the Closed (0%) position
P11.3
Position-
Output
End (at
100%)
0 20.5 mA
{20 mA}
mA value for the On (100%) position
P11.4
Position-
Output
Calib. 20 mA -10% +10%
Calibrating the output position during the setting of
this parameter will output a 20 mA (100%) signal.
Use this parameter to calibrate accurately the
20 mA output signal (e.g., if you measure 19.8 mA
at the output, just add 1% (0.2 mA. . . 1% of 20 mA)
to the displayed value).
7.11 Parameter group: Step mode
Step mode operation can be used to extend the operating time in certain ranges or for the whole travel; it is
available in local, remote and emergency mode.
Step mode operation can be activated individually for the directions OPEN and CLOSED.
Cycle start, cycle end, cycle duration and interval time can be set separately for both directions (see chapter
Figure 62, page 35).
Menu item
Sub-Menu
item
poss. setting Notes / Comments
P12.1
Step mode
function
Mode disabled Step mode operation is disabled
enabled
Step mode operation is enabled in LOCAL,
REMOTE and EMERGENCY operation
Local only Step mode mode is only enabled in LOCAL mode
Remote only Step mode mode is only enabled in REMOTE mode
Local + Remote
only
Step mode mode is enabled in REMOTE and
LOCAL mode
P12.2
Step mode
function
Start Open 0 - 100%
In OPEN direction, position in % from which the
step mode operation should start.
P12.3
Step mode
function
End Open 0 - 100%
In OPEN direction, position in % of which the step
mode operation should end.
continued on next page