7.11
Date Code 20020903 SEL-587Z Instruction Manual
ASCII Command Reference
Command Definitions
MET (Meter)
Access Levels 1, 2
The MET command displays instantaneous magnitudes and phase angles of
the following:
Current magnitudes are displayed in primary amperes. The SEL-587Z reports
the phase angles referenced to IA (IA phase angle = 0, positive phase angles
leading).
To view sequential instantaneous metering values, enter the command:
=>MET n <Enter>
where n is an optional parameter to specify the number of times to repeat the
meter display. n may range from 1 to 32767. If n is not specified, the relay
displays the meter report once:
BUS 1 Date: 02/04/2002 Time: 15:29:43.170
STATION A
87A 87B 87C
V MAG (V) 0 0 0
IA IB IC IG 3I2
I MAG (A) 0 0 0 0 0
I ANG (DEG) 0.00 00.00 00.00 00.00 00.00
=>
MET D (Demand
Ammeter)
Access Levels 1, 2
The MET D command displays the demand and peak demand values of the
following quantities:
Element Description
87A A-phase high-impedance element measured voltage (magnitude only)
87B B-phase high-impedance element measured voltage (magnitude only)
87C C-phase high-impedance element measured voltage (magnitude only)
IA A-phase current in primary amps
IB B-phase current in primary amps
IC C-phase current in primary amps
IG Calculated residual current in primary amps
3I2 Calculated negative-sequence current in primary amps
Quantities Description
Currents I
A,B,C
input currents (A primary)
I
G
Residual ground current (A primary; IG =3I0 = IA + IB + IC)
3I
2
Negative-sequence current (A primary)
Reset Time Demand, peak–last time the demands and peak demands were reset