10.7
Date Code 20020903 SEL-587Z Instruction Manual
Testing and Troubleshooting
Acceptance Testing
=>>STA
BUS 1 Date: 05/13/2002 Time: 12:23:53.231
STATION A
FID=SEL-587Z-R100-V0-Z001001-D20020513 CID=E3D0
SELF TESTS
W=Warn F=Fail
87A 87B 87C IA IB IC MOF
OS 3 3 3 3 3 3 0
+5V_PS +5V_REG -5V_REG +10V_PS -10V_PS VBAT
PS 4.99 5.04 -5.06 10.23 -10.17 3.35
TEMP RAM ROM CR_RAM EEPROM
33.8 OK OK OK OK
Relay Enabled
=>>
Figure 10.3 STA Command.
The STA (Status) on page 7.18 in Section 7: ASCII Command
Reference explains the values listed in the above status
printout.
Step 5. Purpose: View factory settings entered before shipment.
Method: The relay is shipped with factory settings; type SHO
<Enter> to view the settings. The SEL-587Z Settings Sheets in
Section 5: Setting the Relay include a complete description of
the settings. The terminal display should look similar to the
following:
=>>SHO
Relay Settings:
RID =BUS 1
TID =STATION A
CTR = 120 TDURD = 9.000
87A1P = 125 87A2P = 40 87B1P = 125 87B2P = 40
87C1P = 125 87C2P = 40
50P1P = OFF 50P2P = OFF 50P3P = OFF
50A1P = 2.5 50A2P = 1.0 50B1P = 2.5 50B2P = 1.0
50C1P = 2.5 50C2P = 1.0
51PP = OFF 51PC = U3 51PTD = 15.00 51PRS = N
51AP = OFF 51AC = U3 51ATD = 15.00 51ARS = N
51BP = OFF 51BC = U3 51BTD = 15.00 51BRS = N
51CP = OFF 51CC = U3 51CTD = 15.00 51CRS = N
50G1P = OFF 50G2P = OFF
51GP = OFF 51GC = U3 51GTD = 15.00 51GRS = N
50Q1P = OFF 50Q2P = OFF
51QP = OFF 51QC = U3 51QTD = 15.00 51QRS = N
CFD = 60.000
Press RETURN to continue
DMTC = 5 PDEMP = 5.00 GDEMP = 1.50 QDEMP = 1.50
SV5PU = 120.000 SV5DO = 0.000 SV6PU = 15.000 SV6DO = 0.000
SV7PU = 0.000 SV7DO = 0.000 SV8PU = 0.000 SV8DO = 0.000
SV9PU = 0.000 SV9DO = 0.000 SV10PU= 0.000 SV10DO= 0.000
SV11PU= 0.000 SV11DO= 0.000 SV12PU= 0.000 SV12DO= 0.000
SV13PU= 0.000 SV13DO= 0.000 SV14PU= 0.000 SV14DO= 0.000
NFREQ = 60 PHROT = ABC DATE_F= MDY
=>>
Figure 10.4 SHO Command.
The SHO (Showset) on page 7.15 in Section 7: ASCII
Command Reference explains the other settings available with
variations of the SHO command.