D.8
SEL-587Z Instruction Manual Date Code 20020903
Modbus RTU Communications Protocol
Modbus Commands
The relay responses to errors in the query are shown below:
06h Preset
Single Register
Command
The SEL-587Z uses this function to allow a Modbus master to write directly to
a database register. These registers are used to write the command code and
parameters for the command region, selecting the event number or channel
number for Event data region and setting the Relay Date and Time. If you are
accustomed to 4X references with this function code, for six-digit addressing,
add 400001 to the standard database addresses.
Table D.9 SEL-587Z Command Coils
Coil Field
1OUT1
2OUT2
3OUT3
4OUT4
5ALARM
6 RB1
7 RB2
8 RB3
9 RB4
10 RB5
11 RB6
12 RB7
13 RB8
14 Pulse RB1
15 Pulse RB2
16 Pulse RB3
17 Pulse RB4
18 Pulse RB5
19 Pulse RB6
20 Pulse RB7
21 Pulse RB8
Error Error Code Returned
Communication
Counter Increments
Invalid bit (coil) number Illegal Data Address (02h) Invalid Address
Illegal bit
state requested
Illegal Data Value (03h) Illegal Function Code/Op Code
Format error Illegal Data Value (03h) Bad Packet Format