EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-587Z - Equation 3.11

Schweitzer Engineering Laboratories SEL-587Z
276 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.17
Date Code 20020903 SEL-587Z Instruction Manual
Relay Elements
Overcurrent Protection
Reset Time
Equation 3.11
U.S. Very Inverse Curve: U3
Operating Time
Equation 3.12
Reset Time
Equation 3.13
U.S. Extremely Inverse Curve: U4
Operating Time
Equation 3.14
Reset Time
Equation 3.15
U.S. Short-Time Inverse Curve: U5
Operating Time
Equation 3.16
Reset Time
Equation 3.17
I.E.C. Class A Curve (Standard Inverse): C1
Operating Time
Equation 3.18
Reset Time
Equation 3.19
tr TD
5.95
1M
2
----------------
=
tp TD 0.0963
3.88
M
2
1
----------------+ =
tr TD
3.88
1M
2
----------------
=
tp TD 0.0352
5.67
M
2
1
----------------+ =
tr TD
5.67
1M
2
----------------
=
tp TD 0.00262
0.00342
M
0.02
1
----------------------+ =
tr TD
0.323
1M
2
----------------
=
tp TD
0.14
M
0.02
1
----------------------
=
tr TD
13.5
1M
2
----------------
=

Table of Contents