7.20
SEL-587Z Instruction Manual Date Code 20020903
ASCII Command Reference
Command Definitions
where m is:
the Relay Word bits row (1–13) to be displayed or
“0” (zero) to take the targets back to their normal front-panel target
operation or
NOTE: The reset function also occurs
when you type the CAN character
<Ctrl>X on a serial communications
terminal (see SEL ASCII Protocol on
page 6.7 in Section 6: Serial Port
Communications).
“R” to take the targets back to their normal front-panel target operation
(like TAR 0), reset the FAULT TYPE targets (87, 50, 51, A, B, C, and G),
and unlatch the trip logic for testing purposes (See Appendix C: Relay
Word Bits).
where n is:
the number of times to repeat the displaying of the selected Relay Word
bit row on the computer screen connected to the serial port.
If parameter n is not entered, the information displays once on the screen.
Parameter n does not affect the remapping of the front-panel targets. They are
remapped according to parameter M and will stay in that new state until a new
TAR command is executed or the port times out due to port inactivity (see
serial port setting T_OUT in the SHO P F command display sample in
Figure 7.3 on page 7.17). Port timeout takes the targets back to their normal
front-panel target operation (like TAR 0).
If the TAR command is executed from the front panel (See Figure 8.1 on
page 8.2 in Section 8: Front-Panel Interface), front-panel timeout is 15
minutes of front-panel pushbutton inactivity. Front-panel timeout takes the
targets back to the normal front-panel target operation, also (like TAR 0).
Table 7.7 SEL-587Z Relay Word and Its
Correspondence to TAR Command and Front-Panel LEDs
TAR 0
(Front-
Panel
LEDs)
EN 87 50 51 A B C G
TAR1
51P 51PT 51PR 51A 51AT 51AR 51B 51BT
TAR2
51BR 51C 51CT 51CR 51G 51GT 51GR 51Q
TAR3
51QT 51QR * 50P1 50P2 50P3 50A1 50A2
TAR4
50B1 50B2 50C1 50C2 50G1 50G2 50Q1 50Q2
TAR5
87A1 87A2 87B1 87B2 87C1 87C2 * *
TAR6
* * * IN1 IN2 OC CC CF
TAR7
LB1 LB2 LB3 LB4 LB5 LB6 LB7 LB8
TAR8
RB1 RB2 RB3 RB4 RB5 RB6 RB7 RB8
TAR9
SV1 SV2 SV3 SV4 SV5 SV6 SV7 SV8
TAR10
SV9 SV10 SV11 SV12 SV13 SV14 * *
TAR11
TRIP1 TRIP2 TRIP3 CLOSE * PDEM GDEM QDEM
TAR12
SV5T SV6T SV7T SV8T SV9T SV10T SV11T SV12T
TAR13
SVT13T SVT14T * ALARM OUT1 OUT2 OUT3 OUT4