EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-587Z - SEL-587 Z Relay Command Summary; Table 7.8 SEL-587 Z Relay Commands; Table 7.9 SET;SHOW Command Options

Schweitzer Engineering Laboratories SEL-587Z
276 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.22
SEL-587Z Instruction Manual Date Code 20020903
ASCII Command Reference
SEL-587Z Relay Command Summary
SEL-587Z Relay Command Summary
Table 7.8 SEL-587Z Relay Commands
a
a
See the table below for SET/SHOW options.
Command Description
2ACCESS Go to Access Level 2 (complete relay monitoring and control)
ACCESS Go to Access Level 1 (monitor relay)
BNAME ASCII Names of all relay status bits (Fast Meter)
CASCII Generate the Compressed ASCII response configuration message
CEVENT EVENT command for the Compressed ASCII response
CHISTORY HISTORY command for the Compressed ASCII response
CLOSE Access the CC Relay Word bit to close a circuit breaker
CONTROL Set, clear, or pulse an internal remote bit
CSTATUS STATUS command for the Compressed ASCII response
DATE Display and set the date
DNAME ASCII names of all relay digital I/O (Fast Meter)
EVENT Display and acknowledge event reports
HISTORY View event summaries/histories; clear event data
ID Display the firmware identification, part number, and other configuration data
IRIG Update the internal clock/calendar from the IRIG-B input
METER Display metering data and internal relay operating variables
OPEN Access the OC Relay Word bit to open a circuit breaker
PASSWORD Display or change relay passwords
PULSE Pulse a relay output contact
QUIT Reduce access level to Access Level 0 (exit relay control)
SER View Sequential Events Recorder reports
SET
a
Enter relay settings
SHOWSET
a
Display relay settings
STATUS Report or clear relay status
TARGET Display relay elements for a row in the Relay Word table
TIME Display and set the internal clock
TRIGGER Initiate a data capture and record an event report
Ta b le 7.9 S E T/S HOW Com m an d Opt i ons
Option Setting Type
SET/SHOW Relay settings
SET/SHOW L Logic settings
SET/SHOW P 1 Rear port settings
SET/SHOW P F Front port settings
SET/SHOW T Text settngs
SET/SHOW R SER settings

Table of Contents