4.10
SEL-587Z Instruction Manual Date Code 20020903
Control Logic
Remote Control Switches
Settings Change
If relay settings are changed, the states of the remote bits (Relay Word bits
RB1 through RB8) are retained. If a remote control switch is in the ON
position (corresponding remote bit is asserted to logical 1) before a settings
change, it will come back in the ON position (corresponding remote bit is still
asserted to logical 1) after the settings change. If a remote control switch is in
the OFF position (corresponding remote bit is deasserted to logical 0) before a
settings change, it will come back in the OFF position (corresponding remote
bit is still deasserted to logical 0) after the settings change.