Manual – DFE32B Fieldbus Interface PROFINET IO
5
Project planning for the PROFINET IO controller
Project Planning with PROFINET
Copy the required entry to the PROFINET IO system via drag & drop:
Select "MDX61B+DFE32B V1.2" [2] if your controller supports topology detection.
Select "MDX61B+DFE32B V1.2 ALT" if your controller does not support topology
detection.
Assign the name of the PROFINET node.
This name must later correspond to the PROFINET unit name specified in the
DFE32B.
Delete the entry on slot 2 in to perform the project planning for your application. Se-
lect the process data configuration required for your application.
Specify the IO and periphery addresses for the configured data widths and save your
configuration.
The slot model is used for project planning with PROFINET. Each slot is assigned to
a DFE32B communication interface.
Slot 1: Must be assigned "Slot not used" [1]
Slot 2: Process data channel [2]. Number of process data, cyclically exchanged be-
tween PROFINET IO controller and PROFINET IO device.
Extend your user program by data exchange with the new units.
Process data transfer is consistent. SFC14 and SFC15 can be used to transfer pro-
cess data.
68065AEN
[1]
[2]

Table of Contents