Operating Instructions FLOWSIC100
Gas Velocity Monitor
Product Description
8012513/03-2008 © SICK MAIHAK GmbH · Germany · All rights reserved 29
2.3.3 Multi Control Unit (MCU)
The control unit has the following functions:
Control of data transfer and processing the data from the measuring unit(s) connected
via RS485 interface
Signal output via analog outputs (measured value) and relay outputs (device status)
Signal input via analog and digital inputs
Power supply for the connected measuring units via 24 V switching power pack with wide-
range input
Communication with host control systems via optional modules
Plant and device parameters can be set easily and conveniently via a USB interface using a
laptop and the user-friendly SOPAS ET operating software. The parameters are stored
reliably even in the case of a power failure.
The control unit is usually installed in a steel plate housing.
Versions
1. Control unit without purge-air supply.
This control unit serves for the connection of the sender/receiver units FLSE100-M, H,
PR, S, PM, PH and PHS.
Fig. 2.17: Control unit MCU with options
DISPLAYMODUL
relay 3 relay 4 relay 5
BUS - S/E unit 1
BUS
Ter m
Ter m
BUS - S/E unit 2
relay 1
relay 2
com nc. no.com nc. no. com nc. no. com nc. no.com nc. no.
T1A
LED
Option
LC-Display
Operating
keys
Connection-
board
Interface module option I/O module option Display module option